ANSI/AWI 1232-2022 - Manufactured Wood Casework

3.3 Structural

3.3.1 Product Performance Requirements

a) /supplier’s documented fabrication methodologies shall include joinery, material, and component details that have been tested in conformance with AWI Test Methodologies referenced within this standard. Testing shall be conducted by laboratories holding ISO 17025 accreditation or operating under an equivalent quality management system recognized by AWI.

b) In the absence of testing, manufacturer/supplier may defer to AWI’s Tested and Approved Methods and Materials for Casework Construction, available at www.awinet.org/standards

c) Load values expressed within this standard are specific to referenced laboratory tests conducted in accordance with AWI Test Methodologies. These load values do not suggest service loads nor shall they be construed as suggesting normal casework usage loads.

d) Construction methods and materials shall be consistent throughout the project.

e) s which will receive sinks or appliances may be modified as needed, provided structural integrity is retained.

3.3.2 Determination of Product Performance Duty Level

a) Product Performance Duty Level is determined by the lowest tested value derived from AWI Test Methodologies referenced within this standard for joinery methods and materials or components. (Example: A Product may include a construction meeting Performance Duty Level 2 and may also include an adjustable shelf meeting Performance Duty Level 1. The assembled casework unit would then meet Performance Duty Level 1 as the lowest tested value.)

3.3.3 Casework, General

a) For the purposes of s, Wall Cabinets, , Drawer Boxes, Shelves, and Hardware of this standard, the following terms are referenced only as used within the context of the cited test methodologies:

  • Top
  • Bottom
  • Adjustable Shelf
  • Fixed Shelf
  • Drawer
  • Door

3.3.3.1 Base Cabinets

a) Load values expressed within this standard are specific to referenced laboratory tests conducted in accordance with AWI Test Methodologies. These load values do not suggest service loads nor shall they be construed as suggesting normal casework usage loads.

b) Minimum performance requirements according to the AWI BC-1 Base Cabinet Assembled Unit Test Methodology:

 

Component Duty Level 1 Duty Level 2
Top 219.7 kg/sq. m
[45 lb./sq. ft]
341.8 kg/sq. m
[70 lb./sq. ft.]
Adjustable Shelf 122 kg/sq. m
[25 lb./sq. ft.]
195.3 kg/sq. m
[40 lb./sq. ft.]
Doors 45.4 kg [100 lb.] each
Drawers 22.7 kg [50 lb.] each

 

 

c) Minimum performance requirements according to the AWI BC-2 Base Cabinet Structural Integrity Test Methodology:

Component Duty Level 1 Duty Level 2
Top 659.1 kg/sq. m
[135 lb./sq. ft.]
976.5 kg/sq. m
[200 lb./sq. ft.]

 

3.3.3.2 Wall Cabinets

a) Load values expressed within this standard are specific to referenced laboratory tests conducted in accordance with AWI Test Methodologies. These load values do not suggest service loads nor shall they be construed as suggesting normal casework usage loads.

b) Minimum performance requirements according to the AWI WC-1 Wall Cabinet Assembled Unit Test Methodology:

Component Duty Level 1 Duty Level 2
Top 170.9 kg/sq. m
[35 lb./sq. ft.]
244.1 kg/sq. m
[50 lb./sq. ft.]
Adjustable Shelf 170.9 kg/sq. m
[35 lb./sq. ft.]
244.1 kg/sq. m
[50 lb./sq. ft.]
Bottom 170.9 kg/sq. m
[35 lb./sq. ft.]
244.1 kg/sq. m
[50 lb./sq. ft.]

 

c) Minimum performance requirements according to the AWI WC-2 Wall Cabinet Structural Integrity Test Methodology:

Component Duty Level 1 Duty Level 2
Bottom 268.5 kg/sq. m
[55 lb./sq. ft.]
415 kg/sq. m
[85 lb./sq. ft.]
3.3.3.3 Tall Cabinets

a) Load values expressed within this standard are specific to referenced laboratory tests conducted in accordance with AWI Test Methodologies. These load values do not suggest service loads nor shall they be construed as suggesting normal casework usage loads.

b) Minimum performance requirements per shelf (4 and one fixed shelf) according to the AWI TC-1 Tall Cabinet Assembled Unit Test Methodology:

Component Duty Level 1 Duty Level 2
Shelf
(Adjustable and Fixed)
146.5 kg/sq. m
[30 lb./sq. ft.]
219.7 kg/sq. m
[45 lb./sq. ft]

 

c) Minimum performance requirements according to the AWI TC-2 Tall Cabinet Structural Integrity Test Methodology:

Component Duty Level 1 Duty Level 2
Fixed Shelf 512.7 kg/sq. m
[105 lb./sq. ft.]
756.8 kg/sq. m
[155 lb./sq. ft.]

3.3.4 Drawer Box

a) Load values expressed within this standard are specific to referenced laboratory tests conducted in accordance with AWI Test Methodologies. These load values do not suggest service loads nor shall they be construed as suggesting normal casework usage loads.

b) Minimum performance requirements according to the AWI DB-1 Drawer Bottom Compression Test Methodology:

Duty Level 1 Duty Level 2
1112.06 Newtons [250 lbf.]

c) Minimum performance requirements according to the AWI DF-1 Drawer Front Tension Test Methodology:

Duty Level 1 Duty Level 2
889.64 Newtons [200 lbf]

d) At drawer bank cabinets, when the total opening height for drawers exceeds 762 mm [30”], an intermediate front stretcher is required.

3.3.5 Shelves

3.3.5.1 Shelves, Adjustable

a) Load values expressed within this standard are specific to referenced laboratory tests conducted in accordance with AWI Test Methodologies. These load values do not suggest service loads nor shall they be construed as suggesting normal casework usage loads.

b) Performance Duty Level of shelf support system is dependent upon the combination of core material and shelf suspension hardware. Minimum performance requirements according to the AWI SS-1 Shelf Suspension Test Methodology:

Duty Level 1 Duty Level 2
1223.26 Newtons
[275 lbf]
1890.49 Newtons
[425 lbf]

c) Adjustable shelves shall be supported on evenly spaced, cleanly bored holes a maximum of 64 mm [2.520″] on center with shelf rests or on shelf standards with metal shelf rests.

d) Center line of shelf rests, from the front or the back of the interior cabinet body, shall not exceed a minimum of 25.4 mm [1″] to a maximum of 101.6 mm [4”]. The dimension between the center line of the shelf rests shall not be less than 60% of the overall shelf’s depth.

3.3.6 Hardware

a) Hardware shall be fitted and adjusted to ensure operation without binding.

3.3.6.1 Hardware, Drawer

a) Drawer slides shall conform to the following minimum load capacity requirements, as measured per ANSI/BHMA A156.9 (latest edition):

Drawer Type Load Capacity
Pencil drawers 22.7 kg [50 lbs.]
General purpose drawers 34 kg [75 lbs.]
File drawers 45.4 kg [100 lbs.]
Lateral file drawers greater than 610 mm [24”]
and less than 762 mm [30”] in width
68 kg [150 lbs.]
Lateral file drawers equal to or greater than
762 mm [30”] in width
90.7 kg [200 lbs.]
3.3.6.2 Hardware, Locks and Latches

a) Locks shall withstand a minimum of 22.7 kg [50 lb.] pull force in any direction while in the locked position.

b) At locking pairs of doors, the inactive door shall be equipped with a mechanism to prevent opening when in locked position.

3.3.7 Exposed Exterior Surfaces, Decorative Laminate Casework

At exposed exterior surfaces, or TFL shall meet a Resistance to Impact by Large Diameter Ball (ISO 4586-2-2018(E): Test 25) from a distance of:

Duty Level 1 Duty Level 2
375 mm [14.764″] 375 mm [14.764″]

Optimum Climate Controlled Relative Humidity table
Figure 2
Figure 3
Figure 4
Figure 66
Figure 67
Figure 65
3-3-4-1 Epoxy Resin
3-3-4-5 Solid Phenolic
tr-op-table
awi-fig5
ANSIAWI 0620-2018-awi-fig6
ANSIAWI 0620-2018-awi-fig7
awi-fig8
awi-fig9
awi-fig10
awi-fig11
awi-fig12
ANSIAWI 0620-2018-awi-fig13
ANSIAWI 0620-2018-awi-fig14
ANSIAWI 0620-2018-awi-fig23
ANSIAWI 0620-2018-awi-fig25
awi-fig30.ashx
awi-fig41
awi-fig42
ANSIAWI 0620-2018-awi-fig43
awi-fig44
awi-fig45
awi-fig46
ANSIAWI 0620-2018-awi-fig51
ANSIAWI 0620-2018-awi-fig52
ANSIAWI 0620-2018-awi-fig53
ANSIAWI 0620-2018-awi-fig54
formula
awi-fig87
awi-fig5
awi-fig8
awi-fig9
awi-fig10
awi-fig15
awi-fig16
awi-fig17
ANSIAWI 0641-2019-awi-fig18
ANSIAWI 0641-2019-awi-fig19
ANSIAWI 0641-2019-awi-fig20
ANSIAWI 0641-2019-awi-fig21
ANSIAWI 0641-2019-awi-fig22
ANSIAWI 0641-2019-awi-fig23
ANSIAWI 0641-2019-awi-fig24
ANSIAWI 0641-2019-awi-fig25
ANSIAWI 0641-2019-awi-fig26
ANSIAWI 0641-2019-awi-fig27
ANSIAWI 0641-2019-awi-fig28
ANSIAWI 0641-2019-awi-fig29
awi-fig30
ANSIAWI 0641-2019-awi-fig31
ANSIAWI 0641-2019-awi-fig32
awi-fig33
awi-fig34
awi-fig35
ANSIAWI 0641-2019-awi-fig36
awi-fig41
awi-fig42
ANSIAWI 0641-2019-awi-fig43
awi-fig44
awi-fig45
awi-fig46
ANSIAWI 0641-2019-awi-fig72
ANSIAWI 0641-2019-awi-fig85
awi-fig86
awi-fig88
awi-fig89
awi-fig90
awi-fig91
awi-fig92
awi-fig93
awi-fig94
awi-fig95
awi-fig96
awi-fig97
awi-fig98
awi-fig99
awi-fig100
awi-fig102
ANSIAWI 1232-2022-awi-fig5
awi-fig8
awi-fig9
awi-fig10
ANSIAWI 12322022-awi-fig15
ANSIAWI 12322022-awi-fig16
ANSIAWI 1232-2022-awi-fig18
ANSIAWI 1232-2022-awi-fig19
ANSIAWI 1232-2022-awi-fig20
ANSIAWI 1232-2022-awi-fig22
ANSIAWI 1232-2022-awi-fig23
ANSIAWI 1232-2022-awi-fig24
ANSIAWI 1232-2022-awi-fig25
ANSIAWI 1232-2022-awi-fig26
ANSIAWI 1232-2022-awi-fig27
awi-fig28
ANSIAWI 1232-2022-awi-fig29
awi-fig30
ANSIAWI 1232-2022-awi-fig32
awi-fig33
awi-fig34
ANSIAWI 1232-2022-awi-fig35
awi-fig36
ANSIAWI 1232022-awi-fig41
awi-fig42
ANSIAWI 1232-2022-awi-fig43
awi-fig44
awi-fig45
awi-fig46
ANSIAWI 1232-2022-awi-fig72
awi-fig86
ANSIAWI 1232022-awi-fig103
ANSIAWI 1232022-awi-fig104
ANSIAWI 1236-2022-awi-fig5
awi-fig11
awi-fig12
ANSIAWI 1236-2022-awi-fig23
ANSIAWI 1236-2022-awi-fig24
ANSIAWI 1236-2022-awi-fig25
ANSIAWI 1236-2022-awi-fig43
ANSIAWI 1236-2022-awi-fig47
ANSIAWI 1236-2022-awi-fig48
awi-fig50
ANSIAWI 1236-2022-awi-fig110
ANSIAWI 1236-2022-awi-fig111
ANSIAWI 1236-2022-awi-fig112